Technical specifications of MindConnect IoT2040

Functions

Field protocol – S7

Siemens S7 (for S7-3xx / S7-4xx / S7-12xx/ S7-15xx/ ET-200s  PLCs)

Field protocol – OPC UA

Part 8 of the OPC UA specification (Data Access)

Configuration of data collection

With Asset Configuration tool in MindSphere

Data buffering

Up to 500 MB buffering space for collected data

Proxy support

Yes

DHCP support

Yes

Security

Connection outbound via HTTPS on port 443 to MindSphere only; no incoming connection accepted SSL/TLS encryption of data in transit to MindSphere

Installation type/mounting

Design

IoT Gateway, built-in unit

Mounting

DIN rail, wall mounting

Supply voltage

Type of supply voltage

DC 9…36 V, no galvanic isolation

Mains buffering

Mains/voltage failure stored energy time

5 ms

Interfaces

USB port

1x USB 2.0, 1x USB client

Connection for keyboard/mouse

USB / USB

serial interface

2x COM ports (RS 232, RS 485)

Industrial Ethernet

Industrial Ethernet interface

2 x Ethernet (RJ45)

100 Mbps

Yes

1000 Mbps

No

Monitoring functions

Watchdog

Yes

Status LEDs

Yes

EMC

Interference immunity against discharge of static electricity

Interference immunity against discharge of static electricity

±4 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC 61000-4-2

Interference immunity against high-frequency electromagnetic fields

Interference immunity against high frequency radiation

  • 10 V/m for 80 - 1000 MHz, 80% AM acc. to IEC 61000-4-3;

  • 3 V/m for 1.4 - 2 GHz, 80% AM acc. to IEC 61000-4-3;

  • 1 V/m for 2 - 2.7 GHz, 80% AM acc. to IEC 61000-4-3;

  • 10 V for 150 kHz - 80 MHz, 80% AM acc. to IEC 61000-4-6;

Interference immunity to cable-borne interference

Interference immunity on supply cables

  • ±2 kV acc. to IEC 61000-4-4, burst;

  • ±1 kV acc. to IEC 61000-4-5, surge symmetric;

  • ±2 kV acc. to IEC 61000-4-5, surge asymmetric;

Interference immunity on signal cables >30m

±2 kV acc. to IEC 61000-4-5, surge, length > 30 m

Interference immunity on signal cables < 30m

±2 kV in accordance with IEC 61000-4-4, burst, length > 30 m

Interference immunity against voltage surge

Asymmetric interference

±2 kV acc. to IEC 61000-4-5, surge asymmetric

Symmetric interference

±1 kV acc. to IEC 61000-4-5, surge symmetric

Interference immunity to magnetic fields

Interference immunity to magnetic fields at 50 Hz

100 A/m; to IEC 61000-4-8

Emission of conducted and non-conducted interference

Emission of conducted and non-conducted interference

EN 61000-6-4:2007 +A1:2011

Degree and class of protection

IP (at the front)

IP20

Standards, approvals, certificates

Approval

CE (industry), UL, cULus

CE mark

Yes

UL approval

Yes

cULus

Yes

KC approval

Yes

EMC

  • CE

  • EN 61000-6-4:2007 +A1:2011

  • EN 61000-6-2:2005

  • EN 61000-6-3:2007 +A1:2011

  • EN 61000-6-1:2007

Ambient conditions

Ambient temperature during operation

Ambient temperature during operation

0 °C to 50 °C

min.

0 °C

max.

50 °C

Relative humidity

Relative humidity

  • Tested according to IEC 60068-2-78

  • IEC 60068-2-30: Operation: 5 % to 85 % at 30 °C (no condensation)

  • storage / transport: 5 % to 95 % at 25 / 55 °C (no condensation)

Vibrations

Vibration load in operation

Tested according to IEC 60068-2-6: 5 Hz to 9 Hz: 3.5 mm; 9 Hz to 200 Hz: 9.8 m/s²

Shock testing

Shock load during operation

Tested according to IEC 60068-2-27: 150 m/s², 11 ms

Software

MindConnect Software

Pre-installed MindConnect Software

Dimensions

Width

144 mm

Height

90 mm

Depth

53 mm