Technical specifications of MindConnect Nano

Functions

Field protocol – S7

Siemens S7 (for S7-3xx / S7-4xx / S7-12xx/ S7-15xx / ET-200s PLCs)

Field protocol – OPC UA

Part 8 of the OPC UA specification (Data Access)

Configuration of data collection

With Asset Manager in MindSphere

Data buffering

Up to 500 MB buffering space for collected data

Proxy support

Yes

DHCP support

Yes

Security

Connection outbound via HTTPS on port 443 to MindSphere only; no incoming connection accepted SSL/TLS encryption of data in transit to MindSphere

Supply voltage

Type of supply voltage

24 V

Current consumption

max. 1.8 A at 24 V

Mains buffering

Mains/voltage failure stored energy time

20 ms

Interfaces

USB port

1x USB 3.0 / 3x USB 2.0

PCIe slot

1x PCIe x1 (Disabled)

serial interface

1x COM (Disabled)

Video interfaces

Graphics interface

1x DisplayPort (Disabled)

Industrial Ethernet

Industrial Ethernet interface

2x 1000 Mbit RJ45

Monitoring functions

Status LEDs

Yes

Fan

No

EMC

Interference immunity against discharge of static electricity

Interference immunity against discharge of static electricity

±6 kV contact discharge acc. to IEC 61000-4-2; ±8 kV air discharge acc. to IEC 61000-4-2

Interference immunity to cable-borne interference

 Interference immunity on supply cables

  • ±2 kV acc. to IEC 61000-4-4, burst; ±1 kV acc. to IEC 61000-4-5, surge symmetric;

  • ±2 kV acc. to IEC 61000-4-5, surge asymmetric;

Interference immunity on signal cables >30m

  • ±2 kV acc. to IEC 61000-4-5, surge, length > 30 m;

Interference immunity on signal cables < 30m

  • ±1 kV acc. to IEC 61000-4-4; burst; length < 3 m;

  • ±2 kV acc. to IEC 61000-4-4; burst; length > 3 m;

Interference immunity against voltage surge

asymmetric interference

±2 kV acc. to IEC 61000-4-5, surge asymmetric

symmetric interference

±1 kV acc. to IEC 61000-4-5, surge symmetric

Interference immunity against high-frequency electromagnetic fields

Interference immunity against high frequency radiation

  • 10 V/m for 80 - 1000 MHz and 1.4 - 2 GHz, 80% AM acc. to IEC 61000-4-3;

  • 3 V/m for 2 - 2.7 GHz, 80% AM acc. to IEC 61000-4-3;

  • 10 V/m for 10 kHz - 80 MHz, 80% AM acc. to IEC 61000-4-6

Interference immunity to magnetic fields

Interference immunity to magnetic fields at 50 Hz

100 A/m; to IEC 61000-4-8

Emission of conducted and non-conducted interference

Interference emission via line/AC current cables

EN 61000-6-3, EN 61000-6-4, CISPR 22 Class B, FCC Class A

Degree and class of protection

IP (at the front)

IP20

IP (rear)

IP40

Standards, approvals, certificates

CE mark

Yes

UL approval

Yes

UL 508

Yes

cULus

Yes

RCM (formerly C-TICK)

Yes

KC approval

Yes

EMC

CE, EN 61000-6-4:2007, EN 61000-6-2:2005

EN 61000-6-2

Yes

Dust protection

Protection against foreign bodies > 1 mm

FCC

Yes

Marine approval

Germanischer Lloyd (GL)

Yes

American Bureau of Shipping (ABS)

Yes

Bureau Veritas (BV)

Yes

Ambient conditions

Ambient temperature during operation

Ambient temperature during operation

0 °C up to 60 °C

min.

0 °C

max.

60 °C

Ambient temperature during storage/transportation

min.

-20 °C

max.

60 °C

Relative humidity

Relative humidity

Tested according to IEC 60068-2-78, IEC 60068-2-30: Operation: 5% to 80% at 25 °C (no condensation), Storage: 5% to 95% at 25 °C (no condensation)

Vibrations

Vibration load in operation

Tested to DIN IEC 60068-2-6: 10 Hz to 58 Hz: 0.075 mm, 58 Hz to 200 Hz: 9.8 m/s² (1 g)

Shock testing

Shock load during operation

Tested according to IEC 60068-2-27: 150 m/s², 11 ms

Software

MindConnect Software

Pre-installed MindConnect Software

Dimensions

Width

191 mm

Height

100 mm

Depth

60  mm