Permitted mounting positions and surrounding temperature for MindConnect Nano¶
The following mounting positions and surrounding conditional temperature are permitted:
- Horizontal mounting position: The horizontal mounting position is the preferred position. Maximum surrounding temperature is 60°C.
- Vertical mounting position: Maximum surrounding temperature is 50°C.
Note
> 50°C: Install in RAL
- RAL = Restricted Access Location - e.g. a lockable cabinet
Free space around the device¶
Please make sure there’s enough empty space around the device
- Above the device: ≥ 50mm
- Below the device: ≥ 100mm
Note
Maximum height
The maximum altitude to install MindConnect Nano is 4000m.