Permitted mounting positions and surrounding temperature for MindConnect IoT2050

The following mounting positions and surrounding conditional temperature are permitted:

Rail mounting:

  • Horizontal mounting position: The horizontal mounting position is the preferred position. Maximum surrounding temperature is 0 to 40°C.
  • Vertical mounting position: Maximum surrounding temperature is 0 to 50°C.

Wall mounting:

  • Horizontal mounting position: The horizontal mounting position is the preferred position. Maximum surrounding temperature is 0 to 40°C.
  • Vertical mounting position: Maximum surrounding temperature is 0 to 45°C.

>50°C: Install in RAL

RAL = Restricted Access Location - e.g. a lockable cabinet

Free space around the device

Please make sure there’s enough space around the device

  • Above the device: ≥ 50mm
  • Below the device: ≥ 50mm

Last update: January 22, 2024